Kutai EA321

Automatic Voltage Regulator for PMG Generator\r\n\r\nEA321 3 Phase Sensing Permanent Magnet Generator type voltage regulator is a compatible replacement for Newage Stamford MX321 and Onan 305-0823.', '

  • Voltage Regulation < ±0.5% RMS
  • For Use In Parallel Operation
  • RAMP, DIP, DWELL, DROOP, RMS, U/F, Over Voltage & Over Excitation Adjustment Functions
  • Over Exc. / Over Volt. & UFRO LED Indicators
  • Current Limiting Function
Sensing Input Voltage 190~264 VAC 2 phase or 3 phase
Frequency 50/60 Hz selectable
Power Input(PMG) Voltage 170~220 VAC 3 phase 3 wire
Current 3A / phase
Frequency 100~120 Hz nominal
Output Voltage Max. 120 VDC
Current Continuous 4A, Intermittent 7A for 60 sec.
Resistance Min. 15 Ohm
Voltage Regulation < ±0.5% RMS (with 4% engine governing)
Voltage Build-up Residual volts at AVR terminal > 5 VAC
External Volts Adjustment ±10% with 5 K Ohm 1 watt trimmer
Unit Power Dissipation Max. 18 watt
Thermal Drift 0.05% per °C change in AVR ambient
Soft Start Ramp Time 0.4~4 sec.
Analogue Input Max. input ±5 VDC
Sensitivity 1V for 5% generator volts
Input Resistance 1 K Ohm
Droop Input Burden 10 Ohm
Max. Sensitivity 0.22A for 5% droop (PF=0)
Max. Input 0.33A
Under Frequency Protection
(Factory Setting)
Set point 95% Hz
Slope 100~300% down to 30 Hz
Max. Dwell 20% volts/sec. recovery
Current Limit Input Burden 10 Ohm
Sensitivity range 0.5~1A
Over Voltage Detector Input Set point 300V
Time delay 1 sec. (fixed)
CB trip coil volts 10~30 VDC / 0.5 Amp
Over Excitation Protection Set point 120 VDC
Time delay 8~15 sec.
Environment Operating Temperature : -40~70 °C
Storage Temperature : -40~85 °C
Relative Humidity : Maximum 95%
Vibration : 3.3G @ 100~2 KHz
AVR Controls Functions VOLT : Output Voltage Adjustment
STAB : Stability Adjustment
UFRO : UFRO Knee Point Set
DROOP : To Set the Droop to 5% at PF=0
TRIM : To Optimize Analogue Input Sensitivity
EXC : Over Excitation Trip Level Set
DIP : Hz Related Voltage DIP Set
DWELL : Hz Related Recovery Time Set
I LIMIT : Stator Current Limit Set
OVER V : Over Voltage Trip Level Set
RAMP : No Load Voltage Ramp Set Time
RMS : Root Mean Square of Generator
Dimensions 203.0 (L) x 153.0 (W) x 45.0 (H) mm
Weight 530g ±2%
Copyright MAXXmarketing GmbH